Data centers could account for 11.8% of total U.S. electricity by 2030, according to Berkeley Lab’s “United States Data Center Energy Usage Report: 2025 Update.” With numbers like that, electricity is one of a data center’s highest recurring operating costs.
Utility companies bill users, including data centers, for kilowatt-hours (kWh) drawn from the grid, which is yet another reason why data center operators are pushing for highly efficient rack hardware. Between multiple conversion stages, power is repeatedly lost as heat, requiring significant investment to procure and maintain cooling equipment.
A single failure in converter stages, cooling equipment, or poor efficiency alone could cost an extra US$ 50,000 annually. This is why power optimization remains a business decision for data center owners and operators. The article shares how data centers can be optimized for power.
Why is power a bigger problem than compute?
At 8-12 kW, traditional data center rack densities (backed by standard air cooling) were not considered a major engineering challenge. However, with the advent of AI workloads driven by ML hardware in the rack, rack densities have skyrocketed to 100+ kW, and the industry is fast approaching the MW-class IT rack. This challenge is driven by larger multi-trillion-parameter AI models that take longer to train, calling for high-power-density xPUs (GPUs, CPUs, TPUs, etc.) and scale-up architectures.
As AI workloads increase, AI pods are becoming more power-hungry, drawing about 120-150 kW per rack. The entire facility approaches 1-GW power demand, which is roughly the output of a large power plant; enough to support hundreds, perhaps thousands of homes.
In modern AI data centers, the grid’s high-voltage AC power is stepped down to 800 VDC with the disaggregated sidecar rack and sent to the data center compute trays, which then iteratively step it down toward the sub-1-V GPU core voltage. This conversion requires multiple substations, transmission lines, transformers, and power conditioning units.
Many existing [traditional] enterprise data centers cannot deliver and convert this much power. They partner with hyperscalers or compute providers. Utilities often need years to develop and roll out physical infrastructure to run AI infrastructure. This means that power availability is one of the main constraints that decide whether a new data center site can open.
Converting large amounts of power to lower values requires high currents, which leads to heat loss and therefore significant cooling infrastructure. The industry has turned to liquid cooling because it can carry more heat per unit volume than traditional air cooling. However, integrating liquid cooling solutions in data centers disrupts spacing and increases engineering, installation, and management costs.
At the center of the multi-faceted data center design problem is power delivery and management, as it directly affects how quickly operators can secure new grid connections.
Current density problems in data centers
Data centers run on multiple power conversion stages, often starting with kilovolts AC from the utility grid and stepping down to a 48 VDC intermediate bus bar (Figure 1). The 48 VDC bus bar delivers voltage to different rack components—some 12 V, some 3.3 V, 1.8 V, or even 1 V. Each rack would traditionally draw 8-12 kW, calling for ~167 A of current (P=VI).

A few hundred amps weren’t problematic for data center operations. Integration of ML hardware accelerated the draw from 8 kW to 80 kW. With a 48 VDC intermediate voltage, an 80-kW rack would draw ~1667 A, while I2R losses scale the heat dissipation geometrically.
Power Electronics News interview with Vicor’s VP of Strategic Marketing Maury Wood shared how cutting I2R loss is key to power optimization in data centers, as power converters are already highly efficient and easily optimized. Wood said processors, compute accelerators, and trays consume 50% of the rack power, making power delivery to the processor a significant lever.
This shows that power conversion happens at the die level to shorten the current path.
To avoid higher currents and associated I2R losses, data centers are migrating to 400 V bipolar rails (±400 V), first shown in the OCP Mount Diablo specification, where each rail sits at 400 V relative to ground. At 400 V, delivering 80+ kW to the rack isn’t a problem. Currents become much smaller and easier to deal with.
The 48-V dissipates 278x more I2R losses than a ±400-V bus. However, absolute loss also depends on R, which varies with bus bar design.
Nvidia is spearheading the shift to a single rail at 800 VDC where a solid-state transformer (SST) converts AC from the grid to 800 VDC in a single step, eliminating multiple power stages (Figure 2).
As of 2026, many 800 VDC systems remain as a proof-of-concept (POC), but the native 800-VDC architecture is expected to arrive in earnest by 2030.

Board-to-chip: Bottom or sideways?
The length and resistance of the path between the voltage regulator and the processor’s power pins largely determine how much energy is lost as heat in power delivery. Longer paths mean more voltage drop and more I²R loss in PCB traces and planes. Processor boards have traditionally used lateral power delivery (LPD): regulators placed beside the processor (north-south or east-west) send current sideways across the PCB to the xPU. At high currents, losses in this last-inch path can be significant. Empower Semiconductor CEO Tim Phillips estimated that current traveling through the PCB in lateral designs can waste 5% to 20% of system power, loss that moving the regulator closer to the processor eliminates.
Vertical power delivery (VPD) mounts the voltage regulators on the underside of the PCB, directly beneath the processor, so current flows up through the board instead of across it. Instead of flowing sideways, power flows vertically on the backside of the PCB to feed primary rails in the processor, then extends into secondary rails for memory or I/O connections. By shortening the power path, the data center sees lower I2R losses. VPD modules are now shipping in platforms across the industry.
VPD shortens the path to the processor’s package, but current still has to climb through the package and the chip’s own metal stack to reach the transistors. At advanced nodes, that final stretch is becoming a bottleneck of its own.
Inside the die: Backside power delivery
Backside power delivery attacks the same resistive-loss problem as VPD, but at the transistor level. VPD is a board-level architecture that places voltage regulators beneath the processor. Backside power delivery is a wafer-level process technology that moves a chip’s power wiring beneath its transistors.
The power delivery network (PDN) normally remains at the front of the chip. Power has to travel down through many thin, resistive layers to reach the transistors, which causes IR drop, and the power lines take up routing space that signals need. As nodes shrink, interconnects get thinner and more resistive, and routing congestion worsens. Backside power delivery moves the power network beneath the transistors, leaving the front side for signal routing (Figure 3).

Semiconductor manufacturers, including Intel (PowerVia), TSMC (Super Power Rail), and Samsung, aim to introduce backside power delivery features in below-2 nm advanced-node chips. In a 2023 test chip, Intel reported that PowerVia improved platform voltage droop by more than 30%, delivered a 6% frequency benefit, and reached standard cell utilization above 90%.
Taken together, VPD and backside power delivery cut I²R losses at both ends of the last stretch of the path: under the board and under the transistors.